Blogs

Solar inverter between PV DC and AC circuits with separate parallel SPD branches to protective earth

AC vs DC SPD: Key Differences and Can You Swap Them?

The main difference in AC vs DC SPD selection is the supply each device is designed to protect. AC SPDs serve alternating-current distribution circuits. DC SPDs serve direct-current circuits, with versions designed for solar PV, control supplies and other DC applications. Their voltage ratings, protection paths and fault-disconnection arrangements suit those operating conditions. For a replacement, choose a device rated for the circuit’s AC or DC application. A product explicitly rated for

Read More »
Building elevation showing air termination, down conductors, test joints, earth termination and Type 1 SPD

Down conductor and air termination: sizes, spacing and routing

The air termination is the part of a lightning protection system that takes the strike: rods, roof conductors, catenary wires, or roof metal thick enough to do the job. The down conductor carries that current from the roof to the earth termination. For most buildings designed to IEC 62305-3, both are 50 mm² conductors (70 mm² if you use plain aluminium tape), with at least two down conductors around the building

Read More »
Lightning flash current dividing into the earth termination and four supply conductors at the SPD

How to size an SPD: kA rating, Uc and Up, with worked examples

How to size an SPD, or surge protection device, comes down to four numbers. A Type 1 SPD needs an impulse current Iimp that follows from the lightning protection level: 12.5 kA per pole for LPL III and IV, 25 kA for LPL I. A Type 2 SPD needs a nominal discharge current In of at least 5 kA per mode and a maximum discharge current Imax chosen by exposure, with 40 kA the

Read More »
MCB and SPD mounted side by side on a DIN rail

What size MCB for SPD protection? Selection examples

To decide what size MCB for SPD protection to use, start with the SPD manufacturer’s coordination table: select the listed breaker series, current rating and trip curve, then check its breaking capacity against the installation’s prospective short-circuit current. A 32 A or 63 A breaker is a result of that selection. The SPD’s surge rating, such as 40 kA, cannot be converted into an MCB amp rating. First check whether an

Read More »
Scroll to Top

Get In Touch